FLASHING
HIGH WIND TOP
DuraCap TOP
SEE TABLE 2
1 INCH MINIMUM
CLEARANCE
(ALL SIDES)
B-VENT
1 INCH MINIMUM
CLEARANCE
(ALL SIDES)
FIRESTOP
SPACER
DOTTED LINES
SHOW POSSIBLE
OFFSET IN ATTIC
SPACE
Fig 1
ENCLOSURE
CEILING SUPPORT
/ FIRESTOP
VENT CONNECTS
TO APPLIANCE
STORM
COLLAR
II, III, or IV gas appliances. Type B Vent shall not be used to vent flue products
from incinerators, combination gas/oil appliances, oil-fired, or wood-burning
appliances. If there is a question about the use of Type B Vents, contact the
appliance manufacturer or Simpson Dura-Vent's Engineering Department for
further information.
PLANNING
1. Appliances. Carefully review the appliance manufacturer's installation
instructions for positioning the unit, any special venting or connector require-
ments, and verify that it is a Category I appliance or an appliance that requires
the use of Type B gas vent.
2. Placement. The place-
ment of the vent and fittings must
be in accordance with Local
Codes, as well as accepted vent-
ing practices. If more than one
appliance is to be connected to
one venting system, the common
vent must be correctly sized. It is
a good idea to make a sketch of the
proposed installation, labelling
the components you will need.
Adjustable Pipe Lengths are
available to make up odd lengths.
Minimize the number of turns and
lateral runs, as the National Fuel
Gas Code places limitations on
these. A 45° turn is preferable to
a 90° turn. The appliance refer-
ence material should be consulted
at this time, as well as any Local
Authority having jurisdiction. In
most localities, building permits
are required for any new appli-
ances, or modifications to exist-
ing venting systems.